Basic Info.
Model NO.
10-800k
Standby UPS
Sine Wave Output UPS
Output Capacity
Small Type
Equipment Mode
Centralized Model
Brand
OEM
Operating Voltage Range
55~150VAC or 110~300VAC @ 60% Load, 80~145VAC or
Power Factor
0.9
Crest Factor
3:1
Efficiency
95%
Transport Package
Carton
Specification
40kva
Trademark
oem
Origin
China
HS Code
8504402000
Product Description
Industrial UPS-UID Family
10-800kVA
UID Series UPS is a three phase in and three phase out online transformer-based UPS, timely response the strict requirement with high reliability, high load ability, high availability for customer, and provide safe and reliable electric power safeguard.
General Features
Online double conversion
Full DSP control
High power factor
Wide input adaptability
Optimized battery management
N+X parallel redundancy
Strong overload capability
Power walk in
Generator mode
Multi-protection
EPO function
User-friendly network management
Technical Specification
MODEL | EP10 | EP20 | EP30 | EP40 | EP60 | EP80 | ||
Capacity (VA/Watts) | 10kVA / 9kW | 20kVA / 18kW | 30kVA / 27kW | 40kVA / 36kW | 60kVA / 54kW | 80kVA/ 72kW | ||
INPUT | ||||||||
Operating voltage range | 380/400/415Vac (-25% / +20% ), (3Ph+N+PE) | |||||||
Operating frequency range | 50/60Hz(±5%) | |||||||
Power Factor | >0.97 (with filter) | |||||||
OUTPUT | ||||||||
Output Voltage | 380/400/415Vac (±1%) | |||||||
Output frequency | 50/60Hz (±0.05%) | |||||||
Harmonic Distortion (THDv) | <3% with linear load | |||||||
Crest factor | 3:1 (max) | |||||||
Efficiency | ≥88% | ≥89% | ≥90% | ≥90.5% | ||||
BYPASS | ||||||||
Rated voltage | 380/400/415Vac | |||||||
Rated frequency | 50/60Hz | |||||||
Voltage protection range | Upper limit: +20% (+10%,+15%,+20% adjustable)Lower limit: -40% (-10%, -20%, -30%, -40% adjustable) | |||||||
Frequency protection range | ±10% (±2.5%, ±5%,±10%, ±20% adjustable) | |||||||
BATTERY | ||||||||
Battery voltage | 384Vdc ( 360~384Vdc ) | |||||||
SYSTEM FEATURES | ||||||||
Transfer time | 0ms (Line mode →Battery mode) | |||||||
Overload | ≤110%/60min ,≤125%/10min ,≤150%/1min,to Bypass | |||||||
LED display | Input, Inverter, Bypass, Battery, Output, Status | |||||||
LCD display | I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record | |||||||
Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) | |||||||
Optional | Harmonic filter, SNMP adapter, LBS cables, battery temperature sensor,Bypass current-sharing inductor | |||||||
ENVIRONMENT | ||||||||
Operating Temperature | 0ºC~40ºC | |||||||
Storage temperature | -25~55ºC | |||||||
Humidity range | 0~95% (non-condensing) | |||||||
Altitude | <1500m | |||||||
Noise level | <60dB | <65dB | ||||||
PHYSICAL | ||||||||
Dimension W×D×H (mm) | 350×650×1050 | 430×830×1100 | 720×690×1600 | |||||
Net weight (kg) | 148 | 163 | 230 | 255 | 386 | 426 | ||
Shipping weight (kg) | 168 | 183 | 263 | 288 | 432 | 472 | ||
STANDARDS | ||||||||
Safety | IEC/EN62040-1;IEC/EN60950-1 | |||||||
Performance | IEC 62040-3 | |||||||
EMC | IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8;IEC 61000-4-11; |
MODEL | EP100 | EP120 | EP160 | EP200 | EP300 | EP400 | EP500 | EP600 | EP800 | ||
Capacity (VA/Watts) | 100kVA / 90kW | 120kVA / 108kW | 160kVA / 144kW | 200kVA / 180kW | 300kVA / 270kW | 400kVA/ 360kW | 500kVA/ 450kW | 600kVA/ 540kW | 800kVA/ 720kW | ||
INPUT | |||||||||||
Operating voltage range | 380/400/415Vac (-25% / +20% ), (3Ph+N+PE) | ||||||||||
Operating frequency range | 50/60Hz(±5%) | ||||||||||
Power Factor | >0.97 (with filter) | ||||||||||
OUTPUT | |||||||||||
Output Voltage | 380/400/415Vac (±1%) | ||||||||||
Output frequency | 50/60Hz (±0.05%) | ||||||||||
Harmonic Distortion (THDv) | <2% with linear load | ||||||||||
Crest factor | 3:1 (max) | ||||||||||
Efficiency | ≥92% | ≥92.5% | ≥93% | ≥93.5% | ≥94% | ||||||
BYPASS | |||||||||||
Rated voltage | 380/400/415Vac | ||||||||||
Rated frequency | 50/60Hz (auto-sensing) | ||||||||||
Voltage protection range | Upper limit: +20% (+10%,+15%,+20% adjustable)Lower limit: -40% (-10%, -20%, -30%, -40% adjustable) | ||||||||||
Frequency protection range | ±10% (±2.5%, ±5%,±10%, ±20% adjustable) | ||||||||||
BATTERY | |||||||||||
Battery voltage | 384Vdc ( 360~408Vdc ) | 480Vdc | 600Vdc | ||||||||
SYSTEM FEATURES | |||||||||||
Transfer time | 0ms (Line mode →Battery mode) | ||||||||||
Overload | Load≤110%/60min ,≤125%/10min ,≤150%/1min,to Bypass | ||||||||||
LED display | Input, Inverter, Bypass, Battery, Output, Status | ||||||||||
LCD display | I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record, settings | ||||||||||
Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) | ||||||||||
Optional | Harmonic filter, SNMP adapter, LBS cables, battery temperature sensor,Bypass current-sharing inductor | ||||||||||
ENVIRONMENT | |||||||||||
Operating Temperature | 0ºC~40ºC | ||||||||||
Storage temperature | -25~55ºC | ||||||||||
Humidity range | 0~95% (non-condensing) | ||||||||||
Altitude | <1500m | ||||||||||
Noise level | <65db | <70dB | |||||||||
PHYSICAL | |||||||||||
Dimension W×D×H (mm) | 890×775×1600(6P) 1515×830×1600(12P) | 1200×800×1600(6P) 1400×1000×1900(12P) | 1400×1000×1900(6P) 1640×1000×1900(12P) | 2580×1000×1900(500)12P 2800×1040×1900(600)12P | 3280×1040 ×1950(12P) | ||||||
Net weight (kg) | 625/1300 | 685/1450 | 1219/1774 | 1030/1715 | 1560/2395 | 1640/2510 | 3510 | 3950 | 4950 | ||
Shipping weight (kg) | 695/1370 | 755/1520 | 1349/1954 | 1130/1845 | 1690/2545 | 1770/2665 | 3730 | 4250 | 5245 | ||
STANDARDS | |||||||||||
Safety | IEC/EN62040-1;IEC/EN60950-1 | ||||||||||
Performance | IEC 62040-3 | ||||||||||
EMC | IEC/EN62040-2;IEC 61000-2-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8;IEC 61000-4-11; |