- Overview
- Product Description
- Product Parameters
- Dimensions & Mounting
- Application
- Company Profile
- Certifications
- Trade Shows
Basic Info.
Product Description
PMC96S meter is a multi-functional power monitoring meter, it combines function of collecting data and control, and it can replace many kind of meters, relays, transformers and others components. PMC96S can be installed in different positions of electricity distribution system.
Host features |
Instantaneous true RMS value |
Current each single phase and conjunction, average |
Phase voltage/line voltage each single phase and conjunction, average |
Active, reactive, apparent power each phase and the sum of three phases |
Power factor each phase and the sum of three phases |
Frequency 45~65Hz |
Maximum/minimum value |
Max/min rms current |
Max/min rms phase voltage |
Max/min total active, reactive, apparent power |
Max/min total power factor |
Max/min frequency |
Max/min THD I and THD U |
Demand and peak demand value |
Current per phase current value/peak/month end peak |
Total active, total reactive, total apparent power current value/peak/month end peak |
Energy |
Input/output/total active energy 1 pulse output |
Input/output/total reactive energy 1 pulse output |
Apparent electrical energy |
Monthly electrical energy |
Compound rate of electrical energy |
8 multi-rated periods, 4 rates can be set |
Power quality |
Total Harmonic Distortion Rate (THD) current and voltage |
1st-31st harmonic analysis current and voltage |
Voltage crest factor CF and current K coefficient |
Event logging |
100 SOE event records |
Alarm system |
8 configurable limit alarm channels |
4 configurable logical alarm channels |
Communication |
RS-485 /MODBUS-RTU Protocol |
Display |
STN LCD display |
Real-time clock |
Year, month, day, minute, second |
Other |
Program online upgrade supported |
Optional features |
Digital Input (DI) module (optional) |
2 switching inputs |
Digital Output (DO) module (optional) |
2 relay outputs, which can be set by local overrun alarm or controlled remotely |
Analog Input (AI)/Output (AO) module (optional) |
2 channels. 4-20mA DC analog input, 0-5V DC analog input, 4-20mA DC analog output optional. |
Electrical characteristics | ||
System | Three-phase three-wire AC system, three-phase four-wire AC system; | |
Sample rate | 128 samples per cycle | |
Data refresh rate | 1s | |
Measurement accuracy | Current | ±0.2%FS |
Voltage | ±0.2%FS | |
Power | 0.5S | |
Frequency | ±0.001Hz | |
Active energy | 0.5S | |
Reactive energy | 1.0S | |
DC input (AI) | 0.5% FS | |
DC output (AO) | 0.5% FS | |
Voltage input | Measure voltage | 3*220/380V (Direct input) |
3*57.7/100V (PT secondary) | ||
Overload | 1.2x/continuous | |
Input impedance | 300KΩ per phase | |
Current input | Measure current | 5A (CT secondary) or 1A (CT secondary) |
Overload | 1.2x/continuous | |
Input impedance | <0.1Ω | |
Digital input | Operating voltage | 15 VDC |
Input impedance | 12 KΩ | |
Isolation voltage | 2 KV | |
Digital output | Node type | Mechanical contacts |
Node capacity | 220 VAC/5A,30 VDC/5A | |
4~20mA DC input measurement | Measure current | 4~20mA |
Allowed overload capacity | 1.2x/continuous | |
Input impedance | 10 Ω | |
Isolation voltage | 2 KV | |
0~5 V DC input measurement | Measure voltage | 0~5 V |
Allowed overload capacity | 1.2x/continuous | |
Input impedance | 12.5 KΩ | |
Isolation voltage | 2 KV | |
4~20mA DC output | Open-circuit voltage | 15 VDC |
Load capacity | ≤600 Ω | |
Isolation voltage | 2 KV | |
Working power supply | AC | 100~240 VAC/45~65Hz |
DC | 100~375 VDC | |
power consumption | < 3 W | |
Mechanical characteristic | ||
Weight | 0.5 kg | |
IP protection rating | Instrument panel IP52, instrument body IP30 | |
Size | host | 96 *96 * 72 mm |
Host + module | 96 * 96 * 120 mm | |
Operating temperature | display | -20~70°C |
Instrument | -25~70°C | |
Storage temperature | instrument + display | -40~85°C |
Humidity | 5% ~ 90%RH, non-condensing | |
Electromagnetic compatibility | ||
Electrostatic discharge | IEC 61000-4-2, Level 4 | |
Fast transient | IEC 61000-4-4, Level 4 | |
Surges | IEC 61000-4-5, Level 3 | |
Magnetic fields | IEC 61000-4-8, Level 3 | |
Electrical insulation | ||
Insulation resistance | GB/T13729,>50 MΩ | |
AC voltage | GB/T13729, AC 3KV 50Hz /1min | |
Impulse voltage | GB/T13729,5KV,1.2/50us |
The size of the instrument and cutout is shown below (Unit: mm).
Then Embed the meter into the 90mm*90mm cutout slot and screw on the fixing buckle, as shown in the picture followed.
The instrument, as shown in the figure below, is in charge of measuring and collecting power data for each loop and is located in the collection layer. Simultaneously, the instrument equipped with a DI/DO and an AO module may achieve switch status monitoring, relay output, and a transmitter, all of which can be adjusted to your specific requirements.
Kingnen has been focusing on power metering and energy monitoring and management solutions for 20 years. Our products are widely used in the fields of electric power, large-scale buildings and renewable energy, the products have passed UL, CE and other certifications, we have cooperated with the world's top 500 company continously. Last but not least, we provide OEM/ODM services.