Basic Info.
Model NO.
Customized
Cooling Water
Industrial Water
System Type
Open System
Fans Species
Double-speed fan
Noise Level
Low
Application Fields
Industrial
Certification
RoHS, CE
Condition
New
Product Name
Floorstanding Compact Air Dry Refrigeration Cooler
Cooling Capacity
694kw
Water Flow
60L/Sec
Fan Quantity
14PCS
Power Supply
400V-3pH-50Hz
Total Motor Power
38.5kw
Inlet/Outlet Connection
DN125
Inlet Air Temperature
35 Degree C
Inlet/Outlet Water Temperature
60/40 Degree C
Transport Package
Wrap Film/Pallet
Specification
20GP
Trademark
Shenglin
Origin
Shanghai
HS Code
8415901000
Production Capacity
300 Units/Month
Packaging & Delivery
Package Size
1000.00cm * 1000.00cm * 1000.00cm
Package Gross Weight
100.000kg
Product Description
Floorstanding compact Air Dry Refrigeration Cooler and immersion cooling container solution
Features
Technical Data
Fluid cooler SHSL-D1 series parameter(fin space 2.1mm)
Note: Standard SHSL-D1 remote radiator is vertical air discharge, for horizontal air discharge please add "H" in nomenclature, for excmple:SHSL-D1-005H-1X350
Immersion cooling container solution
Case:
Features
Air discharge direction | |
Performance ranges | Cooling capacity: from 5 to 649 kw Air volume: from 2828 to 263503 m3/h Sound pressure level: from 31 to 69 dB A(10m) Fluid coolers:customized on demand |
High efficiency heat exchanger | Capacity designs for maximizing the heat transfer relative to the energy consumption of the fan. Tube and tube coupling design for low pressure drop in the coil on the media sides(maximum 100KPa at water designing condition). Our thermodynamic and aerodynamic designing software is long year tested and proved in Germany |
Fan | Only choose low specific energy consumption fans. Fan nozzle designs for maximum air flow and air throw. Our fans from the world`s leading manufacturer are practically proved to be reliable in operation and long lasting. Motor: protection class IP 54 and insulation class F. Voltage:400V/3N/50Hz Air separator for each fan. |
Testing | Heat exchangers are supplied clean and tested at a pressure of 30 bars |
Options | Coil design refrigerant: water, oil, glycol. Multiple circuits. Sub-cooling circuits. Stainless steel or aluminum casing. Coated aluminum or copper fins. Explosion ploof motor. Customized fin spacing. |
Technical Data
Fluid cooler SHSL-D1 series parameter(fin space 2.1mm)
Type | SHSL-D1-005-1x350 | SHSL-D1-006-1x350 | SHSL-D1-007-1x350 | SHSL-D1-009-1x450 | SHSL-D1-011-1x450 | SHSL-D1-013-1x450 | SHSL-D1-014-1x500 | SHSL-D1-017-1x500 | SHSL-D1-020-1x500 | ||||||
Capacity | Water | 35ºC outdoor temp. | Inlet | 45ºC, | △ | KW | 4.89 | 5.90 | 6.83 | 9.39 | 10.99 | 13.33 | 14.32 | 17.01 | 19.80 |
outlet | 40ºC | Y | |||||||||||||
20% Glycol | Inlet | 45ºC | △ | 4.72 | 5.69 | 6.69 | 8.90 | 10.61 | 13.05 | 13.91 | 16.11 | 19.29 | |||
outlet | 40ºC | Y | |||||||||||||
Medium | Water flow | M3/h | 0.85 | 1.03 | 1.20 | 1.63 | 1.91 | 2.30 | 2.50 | 3.00 | 3.50 | ||||
Pressure drop | kPa | 36.00 | 31.00 | 58.00 | 25.00 | 40 | 80 | 50 | 60 | 40 | |||||
Air flow | △ | M3/h | 2828 | 2712 | 2492 | 6199 | 5827 | 5225 | 8469 | 8168 | 7601 | ||||
Y | |||||||||||||||
Fan motor | Phase | 1 | 1 | 1 | 3 | 3 | 3 | 3 | 3 | 3 | |||||
△ | W | 140 | 140 | 140 | 540 | 540 | 540 | 830 | 830 | 830 | |||||
Y | |||||||||||||||
△ | A | 0.60 | 0.60 | 0.60 | 1.10 | 1.10 | 1.10 | 1.45 | 1.45 | 1.45 | |||||
Y | |||||||||||||||
Fan | No X φ | 1x1x350 | 1x1x350 | 1x1x350 | 1x1x450 | 1x1x450 | 1x1x450 | 1x1x500 | 1x1x500 | 1x1x500 | |||||
Sound pressure level | △ | dB(A) | 31 | 31 | 31 | 43 | 43 | 43 | 49 | 49 | 49 | ||||
Y | 10m | ||||||||||||||
Dimension | L | mm | 870 | 870 | 870 | 1020 | 1020 | 1020 | 1220 | 1220 | 1220 | ||||
W | mm | 525 | 525 | 525 | 625 | 625 | 625 | 825 | 825 | 825 | |||||
H | mm | 797 | 797 | 797 | 820 | 820 | 820 | 870 | 870 | 870 | |||||
A | mm | 690 | 690 | 690 | 840 | 840 | 840 | 1040 | 1040 | 1040 | |||||
B | mm | -- | -- | -- | -- | -- | -- | -- | -- | -- | |||||
C | mm | -- | -- | -- | -- | -- | -- | -- | -- | -- | |||||
D | mm | 490 | 490 | 490 | 490 | 490 | 490 | 490 | 490 | 490 | |||||
Inlet φ | mm | 3/4" | 3/4" | 3/4" | 1" | 1" | 1" | 1-1/4" | 1-1/4" | 1-1/4" | |||||
Inlet φ | mm | 3/4" | 3/4" | 3/4" | 1" | 1" | 1" | 1-1/4" | 1-1/4" | 1-1/4" | |||||
Product weight(empty) | kg | 38 | 42 | 48 | 55 | 60 | 67 | 75 | 82 | 91 |